MDI 100 Amp 4 Pole Contactors

Anderson-Bolds carries 4 pole 100 AMP contractors from MDI

Buy All MDI Contactors HERE.

Mercury Displacement Industries (MDI) Relays are all designed and built to meet the most exacting demands of industry. They have won their high place in the electrical field by doing the tough and tricky jobs that ordinary equipment could at best do in an uncertain manner. They have proved their ability to stand up under the most adverse conditions of temperature, dust and moisture, in all types of applications.

MDI 4100NO Relays - Note Dimensions below
MDI Four Pole Contactors are 10-1/8 Inches wide, 5-5/32 inches high and 2-11/16 wide.

The 100-AMP normally open contactors are designed and manufactured to high quality specifications and the contactors are commonly used in various heating, lighting, and many other industrial applications including high voltage ultraviolet type loads. The contacts are encased in hermetically sealed stainless steel tubes to provide reliable switching for millions of operations. MDI has manufactured this contactor since 1975. It is available in the single, two, three & four pole models.

MDI 4 Pole 100 AMP Contactor Specifications
* CONTACT RESISTANCE .001 ohms
* DIELECTRIC WITHSTAND 2,500 VAC RMS * OPERATE TIME 50 MILLISECONDS
* RELEASE TIME 80 MILLISECONDS

* RATINGS:
CONTACTS: 80 AMP @ 480 VAC

100 AMP @ 240 VAC
RESISTIVE COIL: 120V 50/60 Hz
RESISTANCE: 95 Ω CURRENT: 411 mA
VA: 65.6 WATTAGE: 28.4


* TEMPERATURE RANGE -35° TO +85° C
* COIL TERMINALS #6 BINDING HEAD SCREWS TORQUE TO 7 IN-LB
* LOAD TERMINALS 2-8 AWG COMPRESSION TYPE TORQUE TO 45 IN-LB
* FOUR POLE / SINGLE THROW * MAGNETICALLY ACTIVATED
* MERCURY CONTACTOR 


* LIFE CYCLE ENDURANCE TESTS: U.L. 508 @ 100,00 & CSA 22.2 @ 250,000 CYCLES 

Part numbers are:

4100NO-120A
4100NO-120AH - For Inductive Loads
4100NO-24A
4100NO-24AH - For Inductive Loads
4100NO-220A
4100NO-220AH - For Inductive Loads
4100NO-480A
4100NO-480AH - For Inductive Loads
4100NO-24D
4100NO-24DH - For Inductive Loads


  • 100NO Only - Resistive Loads
  • AC Resistive
    • 240 VAC @ 100 AMPS
    • 480 VAC @ 80 AMPS
    • 600 VAC @ 70 AMPS
  • Tungsten Lamp
    • 120 VAC @ 100 AMPS
  • Motor Loads
    • Single Phase


  • 100NOH - Inductive Loads
  • AC Resistive
    • 240 VAC @ 100 AMPS
    • 480 VAC @ 80 AMPS
    • 600 VAC @ 70 AMPS
  • AC Inductive
    (P.F. 0.4 or Greater)
    • 120 VAC @ 100 AMPS
    • 240 VAC @ 100 AMPS
  • General Purpose
    (P.F. 0.7 or greater)
    • NC 240 VAC @ 80 AMPS
    • NO(H) 240 VAC @ 100 AMPS
    • 480 VAC @ 80 AMPS
  • DC Resistive Heating
    • 48 VDC @ 100 AMPS
    • 125 VDC @ 50 AMPS
    • 250 VDC @ 30 AMPS
  • Tungsten Lamp
    • 120 VAC @ 100 AMPS
  • Motor Loads
    • Single Phase
      • 120 VAC @ 7.5 H.P.
      • 240 VAC @ 10 H.P.
    • Three Phase
      • 240 VAC @ 15 H.P.
      • 480 VAC @ 20 H.P.
MDI Four Pole Contactors are 10-1/8 Inches wide, 5-5/32 inches high and 2-11/16 wide.



Normally Closed relays available upon request. Used mostly for security issues with power outages, Traffic signals and other emergency situations to turn ON batteries or generators.

Contact Anderson-Bolds

Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Wednesday, September 5, 2018

Parker Lead Free Water Steam Valves

Lead Free Steam and Hot Water Valves from Anderson-Bolds

New Lead Free Solenoid Valves from Parker to service the Steam and Hot Water markets.

Call Anderson-Bolds for more information and a quote.  Contact info is HERE!

Parker's Fluid Control Division (FCD) has a long history in manufacturing industry leading steam and hot water valves. Parker has now expanded this offering to include Lead Free Brass valves (containing less than .25% lead) meting the SDWA, Section 1417 requirements for brass. The Parker valves are specifically designed to withstand harsh application conditions.  The steam valves have an integral Stainless Steel orifice for long life and durability.

Lead Free Parker Hot Water and Steam Valves Solenoid Valves

Typical Applications are:

Industrial Dish Washing
Industrial Laundry
Commercial Cooking
Steam Tables
Sterilizers and AutoClaves
Dry Cleaning
Steam Presses
Hotel Laundry
Restaurants

The Valves come in 2 way operation and in either Normally closed or normally open. The Media is water, hot water or steam with valve sizing of 3/8, 1/2, 3/4 and 1 inch ports. The wetted parts are Lead Free Brass, 300/400 series Stainless Steel and copper and either PTFE or EPDM seals.
Depending on size and voltage type the pressure are from 70 to 275 and Cv's up to 12.2.  Water max temperature is 180 degrees F. and steam temperatures to 353 with Class H coils. Steam valves only come in AC voltages.
The standard coils are Nema 4 with a 1/2 inch conduit connection and 18 leads.  Optional coil is the DIN style plug in coil 43850A/ISO 440. Standard voltages are 24, 120 and 240 VAC and 12 and 24 VDC.

AC Valve Body Part Numbers are:
Hot Water
06F25CL332ACF
08F25CL332ACF
12F25CL348ACF
16F25CL364ACF

Steam
06FS5CL432ACF
08FS5CL432ACF
12FS5CL448ACF
16FS5CL464ACF

DC Valve Body Part Numbers are:
Hot Water
06F25CL332A3F
08F25CL332A3F
12F25CL348A3F
16F25CL364A3F