Schneider Robertshaw I-1284 Regulators

Robertshaw Industrial Controls Heating Regulators
Series I-1284 Temperature Regulators - Flange Connections

Contact Anderson-Bolds HERE!

Robertshaw I-1284_Regulator_Valve_Power_Pills















The Robertshaw I-1284-P, Q, S & T Series Temperature Regulators are compact, self-contained and self-powered, three-way control valves especially adaptable to control of water and lubricating oil temperatures on internal combustion engines. The POWER PILL® element, located inside the poppet assembly, responds to the temperature of the medium surrounding it and provides the force necessary to position the poppet as the temperature of the liquid passing through the valve changes. Temperature regulation is achieved by the proportional action of the three-way valve which varies the amount of medium through or bypassing the cooler to maintain the desired temperature. Operation of the POWER PILL elements is unaffected by pressure changes in the system.

The POWER PILLS are factory-set for the specified control temperature and are not manually adjustable. By exchange of POWER PILL elements, the operating temperature may be changed in a very simple manner. Since all internal parts lift out with the valve bonnet, it is not necessary to remove the valve from the piping. The I-1284 series is equipped with a quick-acting manual operator which permits overriding the thermal element if and when abnormal load conditions are encountered in the system. 

Operation: With low temperature liquid surrounding the POWER PILL, the poppet is in the upward position which connects ports "E" and "B." As the temperature increases, the POWER PILL stem extends forcing the poppet downward. When the temperature reaches the control point of the regulator, the valve will be at mid-stroke. If the temperature continues to increase, the poppet will continue to move downward until the by-pass port (B) is completely closed off. 

On the Robertshaw I-1284 a manual crank is provided to override POWER PILL control. Turning the crank counterclockwise moves the poppet upward to close the "C" port. The "B" port may be closed by turning the crank clockwise. In event of power pill failure, the crank should be turned clockwise until the desired cooling is achieved. 

The Robertshaw I-1284 may be installed indoors or out, provided the liquid to be controlled does not freeze. Temperature regulators should be installed as near as possible to the unit being controlled, and a pipeline strainer should be installed upstream.

I-1284-P  3 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-001  75ºF   >>>>  I-1284-P16
Power Pill Repair Element - 2-05V451-101 >>> 96995-A16
2-05V-451-002  80ºF   >>>>  I-1284-P22
Power Pill Repair Element - 2-05V451-102 >>> 96995-A22
2-05V-451-003  90ºF   >>>>  I-1284-P20
Power Pill Repair Element - 2-05V451-103 >>> 96995-A20
2-05V-451-004  100ºF   >>>>  I-1284-P19
Power Pill Repair Element - 2-05V451-104 >>> 96995-A19
2-05V-451-005  110ºF   >>>>  I-1284-P25
Power Pill Repair Element - 2-05V451-105 >>> 96995-A25
2-05V-451-006  120ºF    >>>>  I-1284-P18
Power Pill Repair Element - 2-05V451-106 >>> 96995-A18
2-05V-451-007  130ºF   >>>>  I-1284-P1
Power Pill Repair Element - 2-05V451-107 >>> 96995-A1
2-05V-451-008  135ºF   >>>>  I-1284-P2
Power Pill Repair Element - 2-05V451-108 >>> 96995-A2
2-05V-451-009  140ºF   >>>>  I-1284-P15
Power Pill Repair Element - 2-05V451-109 >>> 96995-A15
2-05V-451-010  150ºF   >>>>  I-1284-P4
Power Pill Repair Element - 2-05V451-110 >>> 96995-A4

I-1284-Q  4 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-011  75ºF   >>>>  I-1284-Q16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-012  80ºF   >>>>  I-1284-Q22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-013  90ºF   >>>>  I-1284-Q20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-014  100ºF   >>>>  I-1284-Q19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-015  110ºF   >>>>  I-1284-Q25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-016  120ºF    >>>>  I-1284-Q18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-017  130ºF   >>>>  I-1284-Q1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-018  135ºF   >>>>  I-1284-Q2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-019  140ºF   >>>>  I-1284-Q15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-020  150ºF   >>>>  I-1284-Q4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

I-1284-S 5 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-021  75ºF   >>>>  I-1284-S16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-022  80ºF   >>>>  I-1284-S22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-023  90ºF   >>>>  I-1284-S20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-024  100ºF   >>>>  I-1284-S19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-025  110ºF   >>>>  I-1284-S25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-026  120ºF    >>>>  I-1284-S18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-027  130ºF   >>>>  I-1284-S1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-028  135ºF   >>>>  I-1284-S2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-029  140ºF   >>>>  I-1284-S15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-030  150ºF   >>>>  I-1284-S4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

I-1284-T 6 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-031  75ºF   >>>>  I-1284-T16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-032  80ºF   >>>>  I-1284-T22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-033  90ºF   >>>>  I-1284-T20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-034  100ºF   >>>>  I-1284-T19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-035  110ºF   >>>>  I-1284-T25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-036  120ºF    >>>>  I-1284-T18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-037  130ºF   >>>>  I-1284-T1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-038  135ºF   >>>>  I-1284-T2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-039  140ºF   >>>>  I-1284-T15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-040  150ºF   >>>>  I-1284-T4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

POWER PILLS REQUIRED per Valve Size
2 inch = 1
2.5 inch = 2
3 inch = 2
4 inch = 2
5 inch = 3
6 inch = 4
Power Pills Supplied with standard part numbers.

Robertshaw makes the below regulators with Bronze Valves
Temperature set points are the same codes.

I-1284-B  2 inch Robertshaw Bronze Regulator
I-1284-C  2.5 inch Robertshaw Bronze Regulator
I-1284-D  3 inch Robertshaw Bronze Regulator
I-1284-E  4 inch Robertshaw Bronze Regulator
I-1284-F  5 inch Robertshaw Bronze Regulator
I-1284-G  6 inch Robertshaw Bronze Regulator

1 = 130
2 = 135
4 = 150
5 = 155
8 = 185
10 = 160
11 = 165
12 = 170
13 = 180
15 = 140
17 = 190
18 = 120
21 = 175
23 = 200

Special Set Points are:
(Extra cost for these)
16 = 75
19 = 100
20 = 90
22 = 80
24 = 60
25 = 110

Robertshaw I-1284 Cooling Regulator Valve


















Robertshaw Industrial Controls is a part of Schneider Electric

Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Robertshaw I-1284...Robertshaw I-1284...Robertshaw I-1284...Robertshaw I-1284

Tuesday, August 13, 2019

ATEX Robertshaw EURO366 Vibration Switch


Anderson-Bolds Sells the Robertshaw EURO 366 VIBRASWITCH

Click HERE for the Robertshaw Vibration Switch Matrix

CONTACT US

VIBRASWITCHMALFUNCTION DETECTOR Model EURO 366 
by Schneider Electric and Robertshaw Industrial


FEATURES AND BENEFITS
  •  Flame Proof (Explosion Proof )
    EEx d IIB/C T6 IP66 T85°C - CESI 03 ATEX 186

  •   Self Powered
    Does not require any form of external power to operate.

  •   Acceleration Sensitive
    Measures total destructive shock, not displacement.

  •   Minimum Maintenance
    No moving parts except when set-point is exceeded.

  •   Continuous Protection
    No attention required after installation.

  •   Ease of Installation
    Requires no special training.

  •   Long Life
    Instrument is rugged and durable - no wearing parts.

  •   Reset
    Manual at unit and choice of remote electrical.

  •   AC or DC
    Reset coil options.

  •   IP66 Enclosure For outdoor and indoor use. 


    EURO366 from Robertshaw















The EURO366 Vibraswitch malfunction detector provides maximum protection from rotating and reciprocating of large motors, pumps or compressors. It is intended for indoor or outdoor use in hazardous or non-hazardous areas with ATEX and CE certifications.


The Model EURO 366 VIBRASWITCHis primarily intended for indoor and outdoor hazardous and non- hazardous areas in those countries requiring ATEX and CE certifications. The EURO 366 employs the same time proven switch design found in Robertshaw's family of vibration switches.

The Model EURO 366 VIBRASWITCHis a vibration sensitive device that protects rotating and reciprocating machinery from extensive damage resulting from mechanical malfunction.When the vibration level of a VIBRASWITCH protected machine exceeds normal by a preselected amount, the normally open contacts of an internal switch close and the normally closed contacts open. This can be used to actuate either an audible warning system or a shutdown circuit before costly damage occurs

Failing bearings, broken blades and similar malfunctions cause increased imbalance or high frequency vibration detectable with the VIBRASWITCH. It is designed for maintenance-free service in permanent installations.

The VIBRASWITCHis an acceleration sensitive instrument that measures the total acceleratory shock present on the machine. Acceleration is a vibration characteristic of prime importance in cases of mechanical failure on reciprocating or rotating machinery. Acceleration is directly related to the shock forces (impact) acting on a machine - thus the VIBRASWITCHoffers a valid measurement of the destructive forces acting on the machine.

Accelerator measurements made by the VIBRASWITCHare the summation of all of the individual accelerations giving a total destructive force acting on the machine - the result is positive protection. 


SPECIFICATIONS
ENVIRONMENTAL
Enclosure
..................... Cast aluminum UNI 4514 alloy 
Weight .......................  2.2 kg (4.9 lb) 
Enclosure Classification........ Flame (Explosion) proof
       EEx-d-IIA/B/C-T6 IP66 T85
Flame Proof Certification.........ESI 03 ATEX 186 
Enclosure Protection................IP66 Standard 
Enclosure Sealing ..................Neoprene o-ring 
Enclosure Finish......... Polyurethane painted olive drab 
Mounting Location.......... Outdoors, unprotected 
External Bolts ................ Stainless steel 
Nameplate .................... Stainless steel 
Conduits .......................2 x 3/4" UNI 6125-74 (will accept 3/4 NPT fitting) 
Ambient Temperature Limits .......... -30C to +85C (-22F to +185F) 
Humidity .............................. To 95% relative humidity @ 37.7C (100F) 
Shock ...................................... 40 g @ 11 ms maximum 


PERFORMANCE
Vibration Measurement Range (Peak)

   Mounted Horizontal....0 to 4.5 g from 0 to 300 Hz
   Mounted Vertical........0 to 3.5 g from 0 to 300 Hz 
Set Point Adjustment ................................. 1 turn per g 
Accuracy ..............5% of full range from 0 to 300 Hz 
Ambient Temperature Effect ........10%/55.5C /(132 F) maximum 


Common Part Numbers are:
EURO366-A0-H2-A-FX-X
EURO366-A2-H2-A-FX-X
EURO366-A4-H2-A-FX-X
EURO366-A7-H2-A-FX-X
EURO366-A8-H2-A-FX-X
EURO366-A9-H2-A-FX-X
↑Above switches are SPDT
↓Below Switches are DPDT
EURO366-D0-H2-D-FX-X
EURO366-D2-H2-D-FX-X
EURO366-D4-H2-D-FX-X
EURO366-D7-H2-D-FX-X
EURO366-D8-H2-D-FX-X
EURO366-D9-H2-D-FX-X


CONTACT Anderson-Bolds - info@anderson-bolds.com

Anderson-Bolds
216-360-9800
www.anderson-bolds.com