Schneider Robertshaw I-1284 Regulators

Robertshaw Industrial Controls Heating Regulators
Series I-1284 Temperature Regulators - Flange Connections

Contact Anderson-Bolds HERE!

Robertshaw I-1284_Regulator_Valve_Power_Pills















The Robertshaw I-1284-P, Q, S & T Series Temperature Regulators are compact, self-contained and self-powered, three-way control valves especially adaptable to control of water and lubricating oil temperatures on internal combustion engines. The POWER PILL® element, located inside the poppet assembly, responds to the temperature of the medium surrounding it and provides the force necessary to position the poppet as the temperature of the liquid passing through the valve changes. Temperature regulation is achieved by the proportional action of the three-way valve which varies the amount of medium through or bypassing the cooler to maintain the desired temperature. Operation of the POWER PILL elements is unaffected by pressure changes in the system.

The POWER PILLS are factory-set for the specified control temperature and are not manually adjustable. By exchange of POWER PILL elements, the operating temperature may be changed in a very simple manner. Since all internal parts lift out with the valve bonnet, it is not necessary to remove the valve from the piping. The I-1284 series is equipped with a quick-acting manual operator which permits overriding the thermal element if and when abnormal load conditions are encountered in the system. 

Operation: With low temperature liquid surrounding the POWER PILL, the poppet is in the upward position which connects ports "E" and "B." As the temperature increases, the POWER PILL stem extends forcing the poppet downward. When the temperature reaches the control point of the regulator, the valve will be at mid-stroke. If the temperature continues to increase, the poppet will continue to move downward until the by-pass port (B) is completely closed off. 

On the Robertshaw I-1284 a manual crank is provided to override POWER PILL control. Turning the crank counterclockwise moves the poppet upward to close the "C" port. The "B" port may be closed by turning the crank clockwise. In event of power pill failure, the crank should be turned clockwise until the desired cooling is achieved. 

The Robertshaw I-1284 may be installed indoors or out, provided the liquid to be controlled does not freeze. Temperature regulators should be installed as near as possible to the unit being controlled, and a pipeline strainer should be installed upstream.

I-1284-P  3 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-001  75ºF   >>>>  I-1284-P16
Power Pill Repair Element - 2-05V451-101 >>> 96995-A16
2-05V-451-002  80ºF   >>>>  I-1284-P22
Power Pill Repair Element - 2-05V451-102 >>> 96995-A22
2-05V-451-003  90ºF   >>>>  I-1284-P20
Power Pill Repair Element - 2-05V451-103 >>> 96995-A20
2-05V-451-004  100ºF   >>>>  I-1284-P19
Power Pill Repair Element - 2-05V451-104 >>> 96995-A19
2-05V-451-005  110ºF   >>>>  I-1284-P25
Power Pill Repair Element - 2-05V451-105 >>> 96995-A25
2-05V-451-006  120ºF    >>>>  I-1284-P18
Power Pill Repair Element - 2-05V451-106 >>> 96995-A18
2-05V-451-007  130ºF   >>>>  I-1284-P1
Power Pill Repair Element - 2-05V451-107 >>> 96995-A1
2-05V-451-008  135ºF   >>>>  I-1284-P2
Power Pill Repair Element - 2-05V451-108 >>> 96995-A2
2-05V-451-009  140ºF   >>>>  I-1284-P15
Power Pill Repair Element - 2-05V451-109 >>> 96995-A15
2-05V-451-010  150ºF   >>>>  I-1284-P4
Power Pill Repair Element - 2-05V451-110 >>> 96995-A4

I-1284-Q  4 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-011  75ºF   >>>>  I-1284-Q16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-012  80ºF   >>>>  I-1284-Q22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-013  90ºF   >>>>  I-1284-Q20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-014  100ºF   >>>>  I-1284-Q19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-015  110ºF   >>>>  I-1284-Q25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-016  120ºF    >>>>  I-1284-Q18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-017  130ºF   >>>>  I-1284-Q1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-018  135ºF   >>>>  I-1284-Q2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-019  140ºF   >>>>  I-1284-Q15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-020  150ºF   >>>>  I-1284-Q4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

I-1284-S 5 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-021  75ºF   >>>>  I-1284-S16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-022  80ºF   >>>>  I-1284-S22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-023  90ºF   >>>>  I-1284-S20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-024  100ºF   >>>>  I-1284-S19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-025  110ºF   >>>>  I-1284-S25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-026  120ºF    >>>>  I-1284-S18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-027  130ºF   >>>>  I-1284-S1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-028  135ºF   >>>>  I-1284-S2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-029  140ºF   >>>>  I-1284-S15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-030  150ºF   >>>>  I-1284-S4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

I-1284-T 6 inch Robertshaw STEEL Regulator
Cooper Energy part numbers below with Temperatures
2-05V-451-031  75ºF   >>>>  I-1284-T16
Power Pill Repair Element - 2-05V451-111 >>> 96995-A16
2-05V-451-032  80ºF   >>>>  I-1284-T22
Power Pill Repair Element - 2-05V451-112 >>> 96995-A22
2-05V-451-033  90ºF   >>>>  I-1284-T20
Power Pill Repair Element - 2-05V443-161 >>> 96995-A20
2-05V-451-034  100ºF   >>>>  I-1284-T19
Power Pill Repair Element - 2-05V443-162 >>> 96995-A19
2-05V-451-035  110ºF   >>>>  I-1284-T25
Power Pill Repair Element - 2-05V443-160 >>> 96995-A25
2-05V-451-036  120ºF    >>>>  I-1284-T18
Power Pill Repair Element - 2-05V443-151 >>> 96995-A18
2-05V-451-037  130ºF   >>>>  I-1284-T1
Power Pill Repair Element - 2-05V443-152 >>> 96995-A1
2-05V-451-038  135ºF   >>>>  I-1284-T2
Power Pill Repair Element - 2-05V451-118 >>> 96995-A2
2-05V-451-039  140ºF   >>>>  I-1284-T15
Power Pill Repair Element - 2-05V443-153 >>> 96995-A15
2-05V-451-040  150ºF   >>>>  I-1284-T4
Power Pill Repair Element - 2-05V443-154 >>> 96995-A4

POWER PILLS REQUIRED per Valve Size
2 inch = 1
2.5 inch = 2
3 inch = 2
4 inch = 2
5 inch = 3
6 inch = 4
Power Pills Supplied with standard part numbers.

Robertshaw makes the below regulators with Bronze Valves
Temperature set points are the same codes.

I-1284-B  2 inch Robertshaw Bronze Regulator
I-1284-C  2.5 inch Robertshaw Bronze Regulator
I-1284-D  3 inch Robertshaw Bronze Regulator
I-1284-E  4 inch Robertshaw Bronze Regulator
I-1284-F  5 inch Robertshaw Bronze Regulator
I-1284-G  6 inch Robertshaw Bronze Regulator

1 = 130
2 = 135
4 = 150
5 = 155
8 = 185
10 = 160
11 = 165
12 = 170
13 = 180
15 = 140
17 = 190
18 = 120
21 = 175
23 = 200

Special Set Points are:
(Extra cost for these)
16 = 75
19 = 100
20 = 90
22 = 80
24 = 60
25 = 110

Robertshaw I-1284 Cooling Regulator Valve


















Robertshaw Industrial Controls is a part of Schneider Electric

Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Robertshaw I-1284...Robertshaw I-1284...Robertshaw I-1284...Robertshaw I-1284

Sunday, October 30, 2011

Coax Valves for Flow Control

Coax Valves from Anderson-Bolds

For over 45 years, the coaxial valves developed by our company have formed a tried and tested element in the control of vacuums and gaseous, liquid, gelatinous, abrasive, contaminated, and aggressive media.

The coaxial valve design allows - as compared to conventional valves - high pressure media to be controlled at high flow rates. Our coaxial valves are available in 2/2 way or 3/2 way versions with threaded or flanged connections. The valves are actuated either by direct-acting solenoid or externally controlled.

  • high cycle life
  • fast actuation
  • compact design
  • maintenance free
  • bi-directional flow
  • pressure balanced
  • back pressure tight
  • installation position optional
  • valves operate from 0 bar upward
  • application with contaminated media


  • co-ax typeorifice
    mm
    connection
    thread NPT
    connection
    flange ANSI
    pressure range
    psi
    Cv
    value
    media
    temperature
    ambient
    temperature
    switch time ms
    open/close
    MK 10DN 101/4 - 3/4-0 - 240 / 6002.9-22°F ... 248°F14°F ... 176°F25 / 25
    MK / FK 15DN 153/8 - 3/4150 / 600 / 15000 - 240 / 600 / 960 / 15005.5-40°F ... 320°F-40°F ... 176°F80 / 80
    MK / FK 20DN 203/4 - 1 1/4150 / 600 / 15000 - 240 / 600 / 960 / 15008.5-40°F ... 320°F-40°F ... 176°F110 / 110
    MK / FK 25DN 251 - 1 1/2150 / 600 / 15000 - 240 / 600 / 960 / 150012.7-40°F ... 320°F-40°F ... 176°F130 / 130
    MK / FK 32DN 321 1/4 - 1 1/2150 / 600 / 15000 - 240 / 600 / 960 / 150016.2-40°F ... 320°F-40°F ... 176°F440 / 250
    MK / FK 40DN 401 1/2 - 2150 / 600 / 15000 - 240 / 600 / 96021.2-40°F ... 320°F-40°F ... 176°F520 / 150
    MK / FK 50DN 5021500 - 24032.2-4°F ... 248°F-4°F ... 176°F400 / 400
    FK 65DN 65-1500 - 24051.8-4°F ... 176°F-4°F ... 176°F600 / 800
    FK 80DN 80-1500 - 24080.5-4°F ... 176°F-4°F ... 176°F600 / 800



    www.anderson-bolds.com

    Thursday, July 15, 2010

    Parker valves, 204/209/304/309 Series

    Parker Solenoid Valves

    Parker Fluid Control Division, manufacturers of the Skinner and Gold Ring lines of solenoid valves and the Sinclair Collins line of process control valves, has introduced an integrated coil for its Series 204 and 304 solenoid valves. Featuring easy installation, the integrated coil is the latest in the division's list of flexible production options for these small yet powerful solenoid valves.

    The patent-pending NEMA 4X coil with rotating conduit hub permits easy installation. The valve lines also include interchangeable AC and DC coils as well as a tab coil for flexible production possibilities. Both the Series 204 and 304 also feature a complete line of high-temperature watertight coil designs to meet the most demanding environmental conditions.

    The Series 204 (two-way) and the Series 304 (three-way) are available as normally closed and normally open valves. Maximized flow rates are delivered through orifice sizes ranging from 1/32" to 5/32". Additionally, the valve line is manufactured with 1/8" port size (NPT) connections.

    The new product lines offer a family of direct-acting solenoid valves for air and liquid (including light oil) applications. These valves meet virtually all of today's commercial, industrial, mobile, instrumentation and medical market needs. State-of-the-art performance characteristics ensure a long life and maximized pressure ratings. Economy models are available for less demanding applications.

    The integrated coil has been evaluated by Underwriters Laboratories and complies with the RoHS (Restrictions of Hazardous Substances) standard under the European Directive 2002/95/EC.

    Visit us online at Anderson-Bolds/Parker

    Tuesday, August 4, 2009

    Solenoid Valves

    Solenoid Valves come in all shapes and sizes and all means of operation. For automation needs, the solenoid valve is the valve of choice.

    This will be a brief discussion of the common solenoid valve used in industry today.

    A solenoid valve is a combination of a valve body the allows a media to flow through it, water, air, oil and a coil that with a voltage applied energizes a magnetic coil to move a plunger that allows the valve to either open or close. Solenoid valves can be signaled by sensors within a plant via an electrical signal thus an operation can then be achieved.

    Solenoid valves come in three basic styles, two way, three way and four way valves. The Two way valves have two ports, an inlet and outlet. The valves can be either normally open or normally closed.
    Normally Closed is the more common style as it requires power to open and will close in a power failure.

    Three way solenoid valves are designed for operating cylinders, air operated control valves and in some cases diverting flow between two directions. 3-way valves can come in normally open, normally closed and universal operation. Universal operation requires a direct acting valve, normally a small size valve, 1/8, 1/4 or 3/8 ports.

    Four way valves are also designed for operating cylinders and valves and can have two solenoids on them, one for each of the two operations.

    The valves can come in different body materials, stainless steel, brass, PVC, Teflon or other. The most common is brass and stainless steel. Seals can be Nitrile, viton, neoprene, or Teflon to name the most common. The different seals have different temperature properties and corrosion resistance.

    Most solenoid valves come with a NEMA 4X coil, good for washdown and submersion in water. Also available are nema 7/9 or explosion proof and DIN style connections.

    Anderson-Bolds stocks valves from Parker and ASCO. We can also provide specialty valves from Valcor.

    www.anderson-bolds.com

    216-360-9800

    Thursday, May 28, 2009

    Anderson-Bolds ~ Since 1934

    Anderson-Bolds has been in the heating and control business since 1934. Mr. A Anderson and Mr. E Bolds joined forces and combined lines to form the firm. The main product line was Chromalox electric heat and soon followed by ASCO solenoid vales and Fenwal Temperature Controls in 1939.

    Throughout the years our goal has been to provide engineering help to our customers whether they are OEM's industrial users or other distributors. We are capable of sizing heaters or drives, providing layouts for snow melting or suggesting automation ideas with our industrial computers or HMI's.

    Anderson-Bolds' sales engineers can figure wattage requirements for any heating job, process or comfort or can figure flow and or Cv for valves, solenoid valves, control valves or jet pumps. We are here to help with your problem applications to provide the correct product for the job.

    Some of our product lines today are Watlow Heaters, Q'Mark Heaters, Toshiba, Fenwal, Parker Valves, Robertshaw Industrial, Meltric, Penberthy, Automatic Timing and Controls, Barksdale, Carlo Gavazzi, Jefferson Valves, Tapeswitch,  Air King Fans and Danfoss.