New Products from Carlo Gavazzi

Anderson-Bolds sells Carlo Gavazzi Automation Products

A couple Newer released products from Carlo Gavazzi

Get a quote HERE!
















CARLO GAVAZZI has launched the new CD34 Series liquid level capacitive sensors. The CD34 Series is designed to detect water-based liquids through non-metallic walls, i.e. plastic or glass. The sensors automatically account for the thickness of plastic or glass walls and compensate for any residual films, moisture or foam accumulation while reliably sensing the presence of the liquid to be detected. The sensor is packed with a universal bracket, which provides great mounting versatility for a variety of surfaces, circular (e.g. sight glass, round containers) or flat.
















CARLO GAVAZZI has unveiled two new single phase AC DIN-rail switch mode power supply families, in housings that are among the most compact available. These new additions to Carlo Gavazzi’s extensive lineup of power supplies include features and price points that are well-suited to a wide variety of markets and applications. The SPDM Series is a general purpose family with industry standard features in the most common output configurations. These smartly priced models are available in ranges from 30W up to 240W, in 12V and 24V outputs, and in housings that are up to 30% smaller than similar types on the market. The SPDC Series offers the highest level of features and performance, in slim metal housings. They feature efficiency levels above 90%, built-in Power Factor Correction, and can provide 150% power boost for up to 3 seconds, making them ideal for applications with high inrush currents. With built-in parallel function and an output ready relay, the SPDC Series helps ensure power is always available for critical functions. These advanced models are available in 120W, 240W, and 480W output versions.

















CARLO GAVAZZI unveiled the new DUB72 Series, a double under voltage monitoring relay that is approved for use in Class I Division 2 hazardous locations. This relay can be used to help prevent brownouts in 24 VDC supplied systems in any kind of application, including hazardous environments. The DUB72 features two independent set levels and outputs, which allow the use of one as a pre-alarm and the second one as an alarm. With a high powered electromechanical 20 amp relay, the second threshold / relay can be used to directly disconnect a battery or load. Its low-profile DIN housing can fit into electrical distribution panels as well as into industrial cabinets.


Get a quote HERE!

Anderson-Bolds
216-360-9800
www.anderson-bolds.com


Thursday, August 9, 2018

Carlo Gavazzi Earth Leakage Monitors

Carlo Gavazzi Earth Leakage (grounding) Monitor Relays

For quotes and information, please go to our Contact Anderson-Bolds page  HERE.


CARLO GAVAZZI is proud to announce the launch of two new Earth Leakage Monitoring Relays, the DEA71 and DEB71. When used in conjunction with a CTG Series Core Balance Current Transformer and appropriate circuit breaker, they provide machine protection against fault currents, and help to reduce fire hazards. These earth leakage relays react to small changes in current which can occur due to insulation or grounding failure.
Two models, each offering choices of threshold ranges, allow users to find the right solution for their unique requirements. The DEA71 features fixed trip levels which offer time-saving installation, with a reliable tripping level and safety against tampering. The DEB71 provides ability to adjust trip levels and includes an adjustable time delay; a lockable front cover provides further tamper protection.
A key advantage offered by DEA71 and DEB71 is avoidance of nuisance tripping in the circuit, in accordance with the EN 60947-2 Annex M norm. Two separate alarm outputs allow for a warning signal to be generated before a shutdown is necessary. Their compact (35mm wide) housing preserves valuable panel space.
The DEA71 and DEB71 from Carlo Gavazzi perform crucial monitoring of earth leakage, prolonging machine life by limiting damage from ground faults as well as reducing fire risk. They conform to global standards such as UL 508, CSA C22.2 and EN 60947-2 Annex M.
The features of the DEA71 and DEB71 Earth Leakage Relays include:
 page1image14184
  •   DEA71 includes two models with fixed trip setting: 30 mA and 300 mA
  •   DEB71 includes two models with adjustable trip levels: 30 mA to 5 A and 300 mA to 30 A
2 SPDT relay outputs, for warning and for alarm 24 VAC to 240 VAC power supply
NORM DIN-rail housing 35 mm
Lockable lid on adjustable models (DEB71)
The DEA71 and DEB71 Monitors and CTG Series Core Balance Current Transformers are available from 

Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Wednesday, July 4, 2018

SSAC/Littelfuse Voltage Monitor HLMUDLAAA

Voltage Monitor Protection Relay HLMUDLAAA from Anderson-Bolds
Made by Littelfuse

Contact Anderson-Bolds

LittelFuse SSAC Voltage Monitor HLMUDLAAA is a universal voltage monitor. 10 amp output relay rating. The HLM Voltage Monitor senses over or under voltage AND phase unbalance and frequency fluctuations and trips if any go oout of range. The Voltage Monitors are currently made by Little Fuse. UL, CSA and CE. Previous manufacturers were SSAC, Entrelac, ABB and Sycom.

BUY the HLMUDLAAA


The HLMU Series is a universal voltage, encapsulated, 3-phase voltage monitor. It continuously measures the voltage of each of the three phases with microcontroller accuracy and compares the value to preset trip points. It separately senses phase reversal and loss; over, under and unbalanced voltages; and
over or under frequency. Protection is assured during periods of large average voltage fluctuations, or when regenerated voltages are present. The unit trips within 200ms when phase loss is detected. Adjustable time delays are included to prevent nuisance tripping and short cycling of sensitive equipment. The isolated, 10A, DPDT relay contacts trip when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage unbalance, and time delays are knob adjustable. The phase loss setpoint and the acceptable frequency range are fixed. Both delta and wye systems can be monitored; no connection to neutral is required.


Voltage Monitor HLMUDLAAA


BENEFITS
Constant monitoring to protect against phase loss, phase reversal; over, under, and unbalanced voltage; over and under frequency
Flexibility to work in 200 to 480VAC applications
Installation flexibility
Provides diagnostics of relay, fault and time delay status
Protects against shock, vibration, and humidity Meets IEC 61000 safety requirements

Operation
Upon application of line voltage, the output is de-energized
and the restart delay begins. If all the three-phase voltages are within the acceptable range, the output energizes at the end
of the restart delay. The microcontroller circuitry automatically senses the voltage range, and selects the correct operating frequency (50 or 60Hz). The over and under voltage trip points are set at ± 10% of the adjusted line voltage. When the measured value of any phase voltage exceeds the acceptable range limits (lower or upper) the trip delay begins. At the end of the trip delay the output relay de-energizes. If the phase voltage returns to an acceptable value before the trip delay expires, the trip delay is reset and the output remains energized. Under, over, and unbalanced voltages plus over or under frequency must be sensed for the complete trip delay before the unit trips. The unit trips in 200ms when phase loss or reversal are sensed. The unit will not energize if a fault is sensed as the line voltage is applied. 


Reset: Reset is automatic upon correction of the voltage or frequency fault or phase sequence.


Restart Delay Options
L = Lockout or minimum OFF time. The restart delay begins when the output trips. The unit cannot be re-energized until the restart delay is complete. This provides a minimum off time
or lockout time to allow equipment sensitive to short cycling, time to reset. If the fault is corrected after the restart delay is complete, the output energizes immediately. The restart delay also occurs when line voltage is applied/reapplied.
R = Restart Delay on fault correction. The restart delay begins when line voltage is reapplied or when a voltage fault is corrected. This option is normally selected when staggered restarting of multiple motors on a power system is required.
N = No Restart Delay. 0.6 second initialization delay on application of line voltage applies.
Restart Notes: All restart options remain reset when the following conditions are detected:
1. Phase loss (phase unbalance greater than 25%) 2. Average line voltage less than 120VAC
3. Phase reversal

The restart delay begins when the condition is corrected.


LED Operation
The LED flashes green during the restart delay, then glows green when the output energizes. It flashes red during the trip delay then glows red when the output de-energizes. It flashes red/green if phase reversal is sensed. If a fault is sensed during the restart delay, the LED will glow red during that portion or the full restart delay. 


Type

3-phase delta or wye with no connection to neutral


Range
240 380 480
Voltage Adj. Range
200-240VAC 340-420VAC 400-480VAC
Frequency
50 or 60Hz 50Hz 60Hz

Line Voltage Max.
550VAC
AC Line Frequency
50/60 Hz automatically detected
Phase Loss
≥ 25% unbalance
Response Time
≤200ms 

Overvoltage Trip Voltage 
109 - 113% of the adjusted line voltage
 Reset Voltage
-3% of the trip voltage

Undervoltage Trip Voltage
88 - 92% of the adjusted line voltage
Reset Voltage
+3% of the trip voltage 

Voltage Unbalance Trip Setpoint
Adjustable 2 - 10% or specify fixed unbalance of 2 - 10% in 1% increments
Reset on Balance
-0.7% unbalance
Trip Delay Active On
Over/under voltage, voltage unbalance, over/under frequency

Range
Adjustable from 1 - 30s or specify fixed delay 1 - 30s in 1s increments
Tolerance
±15%
Restart Delay Range
Adjustable from 0.6 - 300s; if no restart delay is selected a 0.6s initialization delay applies 

Tolerance


±15%
Over/Under Frequency
±4%; Reset ±3%; 50/60 Hz
Phase Sequence
A, B, C, L1, L2, L3
Response Time-Phase
Reversal & Phase Loss
≤200 ms
Reset
Automatic

Output 

Isolated Electromechanical Relay


DPDT


10A resistive @ 240VAC;
8A resistive @ 277VAC; NO-1/4 hp @ 120VAC; 1/3 hp @ 240VAC

Protection
Phase Reversal/Failure

ASME A17.1 Rule 210.6
Motors and Generators
NEMA MG1 14:30, 14:35
Surge
IEEE C62.41-1991 Level B
Isolation Voltage
≥ 2500V RMS input to output
Circuitry
Encapsulated

Dimensions
H 76.7 mm (3.0”); W 50.8 mm (2.0”);
D 41.7 mm (1.64”)

Termination
Screw terminal connection up to 12 AWG (3.3 mm2) wire
  
 Temperature
 -40° to 60°C / -40° to 85°C

BUY the HLMUDLAAA
www.anderson-bolds.com
Anderson-Bolds
216-360-9800

Monday, February 10, 2014

Nematron M1500SRT Sunlight Readable Flat Panel

Nematron M1500SRT Sunlight Readable Flat Panel ~ NEW 

Contact Us!


M1500SRT Sunlight Readable Industrial Flat Panel Monitors with 15” High Bright LED-backlit Display
The M1500SRT industrial monitor is the introductory model in Nematron's line of Sunlight Readable panel mount monitors. The M1500SRT is ideal for harsh applications that may have bright ambient lighting, but may also require the ruggedness of an industrial monitor.



The M1500SRT features a 1500 Nit LED-backlit display. With significantly higher brightness than standard CCFL-backlit displays, the M1500SRT maintains high contrast in bright direct or indirect sunlit conditions. The auto-sensor feature automatically adjusts the display brightness according to bright or dim conditions, reducing user eye strain, especially in dimly lit conditions. Toggle buttons on the front bezel make it convenient for a user to adjust display brightness up or down.

The M1500SRT uses analog resistive touchscreen technology, which allows the use of gloved hands and also alleviates pooled water concerns that capacitive-type touchscreens struggle with in outdoor conditions, such as rain exposure. M1500SRT is also offered with a non-touch, clear polycarbonate window.
The M1500SRT is tested and approved for Class I Div 2 hazardous locations when installed in a NEMA type enclosure with appropriate wiring methods.

Standard Features:
  • 15" XGA Color TFT LED-backlit Display
  • 1500 Nit High Contrast Display
  • 5-wire Ultra-clear Analog Resistive Touchscreen
    - Optional Non-Touch clear polycarbonate window
  • Ultra-Thin panel mounting depth, 2.4" behind bezel
  • User-adjustable brightness toggle buttons on front bezel
  • Auto-sensor for manual or auto adjusting brightness based on brightly or dimly lit conditions
  • Manual Standby button
  • NEMA 4/4X/12 front bezel
    - Optional 304 stainless steel front bezel
  • Integral 100-240 VAC power supply
    - Optional isolated 24 VDC input power
  • Simplified installation with no studs
  • Accepts analog 15-pin video input or DVI input
    - VESA 1 compliant - modes up to 16 million colors
  • RS-232 or USB interface for touchscreen
  • UL and cUL Ordinary Locations Listed 
  • UL and cUL Hazardous Locations Listed
    - Class I Division 2, Groups A, B, C, & D; Class II Division 2, Groups F & G; Class III when mounted in a NEMA enclosure
  • FCC & CE Compliant
  • 2-Year warranty

UL Approvals - Ordinary Locations
cUL Approvals - Ordinary Locations
CE Declaration
UL Approvals - US Class I, Div 2 Approvals
cUL Approvals - Canada Class I, Div 2 Approvals

Display Diagonal15.0" (381.0mm)
Display Sizes
(Active Area H x V)
11.97" x 8.98"
(304.0mm x 228.1mm)
Native ResolutionXGA, 1024 x 768
Displayable Colors16M
Brightness, Typical1500 Nit 1 (minimum)
Contrast Ratio, Typical600:1 (through touchscreen)
Horizon/Vertical View
Angle, CR>5, Typical
160°/160°
Backlight Life, Typical50,000 hrs


216-360-9800

Wednesday, June 2, 2010

TRC Digital Voltage Monitor ~ New-2010

TRC Digital Voltage Monitor AECM 20020

This compact, easy to use instrument is made with advanced microelectronics and
provides accurate testing and monitoring of electrical outlets and systems. Constantly
monitors voltage and frequency indicating potential improper polarity and ground
wiring. Its small size and rugged construction allows for convenient installation in an
electrical outlet or use as a portable service tool.
Voltage is measured as RMS which is much more precise than AC average. RMS
metering is the only method that can accurately measure all AC power sources. The RMS
voltage and frequency readings are ideal for monitoring modified sine waves such as
solid-state generators, inverters and Uninterruptible Power Supply (UPS) products.
The Digital Monitor display will alternate between line voltage in RMS volts and
line frequency in Hertz. The LCD display shows an “F” in front of the reading to denote
frequency.
Three display modes are available:
Alternating Voltage & Frequency( VOLT/FREQ.)
Voltage only (VOLTAGE)
Frequency only (FREQUENCY)
Pressing the MODE button on the front of the Digital Monitor will cycle through the
display modes.
Both voltage and frequency are constantly monitored regardless of the
display mode.


FEATURES
AECM20020
Accurate Testing and Monitoring of All AC Power Source Types
RMS Voltage and Frequency Meter
Multi-tone Fault Alarm
Hands-free Auto Reset
Advanced Microelectronics
One Button Operation
Wiring Diagnostics
LCD Display with LED Backlight


TECHNICAL DATA
Voltage Range 85 to 150 Vac RMS
Frequency Range 40 / 80 Hz
Operating Current 0.02 Amp
Under Voltage Alarm <102>135 Vac RMS
Under Frequency Alarm <55>65 Hz
Outlet Type 120V/15A single phase
Operating temperature +32°F to +125°F

Anderson-Bolds stocks TRC products

216-360-9800