Saturday, May 30, 2020

Fenwal Detect-A-Fire ATEX Rated

ATEX Rated Fenwal Fire Detectors from Anderson-Bolds

For a Quote, use our Fenwal Parts Form HERE!


DESCRIPTION
The Heat Detector Assembly includes part number 17343-124
Heat Detector and Field wire Terminal housing. The assembly is
available in two orientations: Right as part number 03-17343-
127; Left as part number 03-017343-126. The internal connections
are the same in both styles. For additional details on
the Heat Detector, refer to the Operation and Maintenance

Instructions for Fire / Overheat Detector for Series 17343-124.
















IECEx Conditions of Certification:
The enclosure shall be installed to a flat rigid surface
using the mounting means provided.
All conductors/cables shall be suitable for a temperature
of 200°C.
All cable/conduit fittings shall be certified equivalent
to the marking on the apparatus and have a
minimum IP54 rating.
Not more than one single or multiple strand lead
shall be connected into either side of any terminal,
unless multiple conductors have been joined in a
suitable manner, e.g. two conductors into a single
insulated crimped boot lace ferrule.
Leads connected to the terminal shall be insulated
for a minimum 125V and the insulation shall extend
to within 1mm of the metal terminal throat.
All terminal screws, used or unused, shall be tightened
down.













The Fire Detectors come in 5 temperature set points.
140ºF, 325ºF, 425ºF, 600ºF and 725ºF
The Detectors are color coded for Temperature by bands on the tip of the detector shell 17343-124
No Band is 140ºF
Red Band is 325ºF
Green Band is 425ºF
Orange Band is 600ºF
Gray Band is 725ºF




























INSTALLATION

Refer to the following steps for proper installation of the Heat
Detector assembly:
Recommendation: For best support, use rigid conduit when
installing the heat detector field wiring.
1. After proper mounting of the Heat Detector Housing,
unscrew the enclosure cover, exposing the field wire terminals.
2. Ensure the connections between the Heat Detector and
Terminal Block have not become loose during shipping,
tighten as required.
3. Strip 0.3" (7.6mm) of the insulation from the ends of
Input connection A & B.
4. Insert field wire through port.
5. With a flat tip .14 (3.6mm) screw driver, loosen Input connection
A & B set screw.
6. Insert the exposed end of input connection A and B into
the terminal block as shown.
7. Tighten locking screws hand tight plus 1/4 turn.
8. Thread Heat Detector cover hand tight and tighten.
9. Secure cover in place by tightening the locking set screw
located within the cover with a 1/16 (4.2mm) hex “Allen”
wrench.
















For a Quote, use our Fenwal Parts Form HERE!

Anderson-Bolds
216-360-9800

Fenwal Fire Detectors 17343...Fenwal Fire Detectors 17343...Fenwal Fire Detectors 17343...

No comments:

Post a Comment