Vertical Fenwal Detect-A-Fire Switches

Anderson-Bolds stocks Fenwal Detect-A-Fire Switches

Fenwal Vertical Detect-A-Fire (DAF) switches are mounted to the ceiling to detect temperature rise and either turn off a machine or allow for sprinklers or other release devices to put out a fire.

Buy Vertical Detect-A-Fire Units HERE!

VERTICAL DETECT-A-FIRE-UNITS
Fenwal Vertical detectors are designed for use in both "ordinary" or "hazardous" locations. For "ordinary" use, they may be mounted to any approved junction box with 7/8" diameter opening by using 1/2-14 NPT mounting nuts. The device may be wired in or out of conduit, depending on local preference and codes. Four lead wires are provided on normally open vertical units (that close on temperature rise), per UL requirement, to facilitate supervision of system wiring. Instruments are Underwriters Laboratory and Underwriters Laboratory of Canada listed and Factory Mutual (FM) approved for hazardous locations, when mounted in a suitable fitting.

Fenwal Part Numbers include : 27120 28020 27121 28021
Temperature Settings (degrees F): 

140 160 190 210 225 275 325 360 450 500 600 750


Fenwal DETECT-A-FIRE® (D-A-F) thermal detectors are UL Listed (UL of Canada available upon request), and FM Approved detection and release devices for use with fire detection systems to activate alarms and extinguishing systems. This Rate Compensated device combines the best features of both fixed temperature and rate-of-rise detectors. 

Normally Closed, Open on Rise Switches (Click to View)
Fenwal Detect-A-Fire model 12-E27120-000-140 has a set point of 140 degrees F
Fenwal Detect-A-Fire model 12-E27120-000-160 has a set point of 160 degrees F
Fenwal Detect-A-Fire model 12-E27120-000-190 has a set point of 190 degrees F
Fenwal Detect-A-Fire model 12-E27120-000-210 has a set point of 210 degrees F
Fenwal Detect-A-Fire model 12-E27120-000-225 has a set point of 225 degrees F
Fenwal Detect-A-Fire model 12-F27120-000-275 has a set point of 275 degrees F
Fenwal Detect-A-Fire model 12-F27120-000-325 has a set point of 325 degrees F
Fenwal Detect-A-Fire model 12-F27120-000-360 has a set point of 360 degrees F
Fenwal Detect-A-Fire model 12-G27120-000-450 has a set point of 450 degrees F

Fenwal Detect-A-Fire model 12-E27120-022-140 has a set point of 140 degrees F
Fenwal Detect-A-Fire model 12-E27120-022-160 has a set point of 160 degrees F
Fenwal Detect-A-Fire model 12-E27120-022-190 has a set point of 190 degrees F
Fenwal Detect-A-Fire model 12-E27120-022-210 has a set point of 210 degrees F
Fenwal Detect-A-Fire model 12-E27120-022-225 has a set point of 225 degrees F
Fenwal Detect-A-Fire model 12-F27120-022-275 has a set point of 275 degrees F
Fenwal Detect-A-Fire model 12-F27120-022-325 has a set point of 325 degrees F
Fenwal Detect-A-Fire model 12-F27120-022-360 has a set point of 360 degrees F 
Fenwal Detect-A-Fire model 12-G27120-022-450 has a set point of 450 degrees F













Coupling Head, Normally Closed, Open on Rise Switches
Fenwal Detect-A-Fire model 12-E28020-003-140 has a set point of 140 degrees F
Fenwal Detect-A-Fire model 12-E28020-003-160 has a set point of 160 degrees F
Fenwal Detect-A-Fire model 12-E28020-003-190 has a set point of 190 degrees F
Fenwal Detect-A-Fire model 12-E28020-003-210 has a set point of 210 degrees F
Fenwal Detect-A-Fire model 12-E28020-003-225 has a set point of 225 degrees F
Fenwal Detect-A-Fire model 12-F28020-003-275 has a set point of 275 degrees F
Fenwal Detect-A-Fire model 12-F28020-003-325 has a set point of 325 degrees F
Fenwal Detect-A-Fire model 12-F28020-003-360 has a set point of 360 degrees F
Fenwal Detect-A-Fire model 12-G28020-003-450 has a set point of 450 degrees F








  • Hazardous Locations: For Class I, Division 1 and 2 locations install the D-A-F Unit in a listed explosion-proof enclosure with a minimum thread engagement of five full turns. No non-conductive material is to be placed on the threaded joint of the D-A-F Unit or in the listed explosion-proof enclosure. For Division 2 locations assure that a protective ground terminal is provided in the listed explosion-proof enclosure when flexible metal conduit is used.


  • Non-Hazardous Outdoor Locations: Mount the D-A-F in a Listed NEMA Type 3 outlet box, cover and conduit, with 1/2- 14 NPT threads and a minimum thread engagement of 5 full turns. Use pipe plugs with RTV silicone rubber sealant, a rubber gasket and self- sealing screws to attach the cover, and PTFE thread sealtape on the D-A-F threads. For additional requirements consult the local fire department, the National Electric Code and/or the local authority having jurisdiction in the area.


As part of the recommended maintenance procedure, perform a visual inspection of the Fenwan DETECT-A-FIRE® unit in accordance with NFPA 72 guidelines. During the visual inspection, verify that the sensing shell is free of dents, dings or build up of foreign matter of any kind. If the shell is dented or shows signs of any physical damage, replace the unit immediately. If a build up of dust has accumulated on the unit, clean the unit with a vacuum or soft dry cloth. If the shell has been painted, replace the unit. Be careful not to damage the unit in any way.
Note: Some units are factory coated. Do not confuse these with units that were painted by the owners. 

Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Fenwal Vertical Detect-A-Fires...Fenwal Vertical Detect-A-Fires...Fenwal Vertical Detect-A-Fires

Saturday, May 30, 2020

Fenwal Detect-A-Fire ATEX Rated

ATEX Rated Fenwal Fire Detectors from Anderson-Bolds

For a Quote, use our Fenwal Parts Form HERE!


DESCRIPTION
The Heat Detector Assembly includes part number 17343-124
Heat Detector and Field wire Terminal housing. The assembly is
available in two orientations: Right as part number 03-17343-
127; Left as part number 03-017343-126. The internal connections
are the same in both styles. For additional details on
the Heat Detector, refer to the Operation and Maintenance

Instructions for Fire / Overheat Detector for Series 17343-124.
















IECEx Conditions of Certification:
The enclosure shall be installed to a flat rigid surface
using the mounting means provided.
All conductors/cables shall be suitable for a temperature
of 200°C.
All cable/conduit fittings shall be certified equivalent
to the marking on the apparatus and have a
minimum IP54 rating.
Not more than one single or multiple strand lead
shall be connected into either side of any terminal,
unless multiple conductors have been joined in a
suitable manner, e.g. two conductors into a single
insulated crimped boot lace ferrule.
Leads connected to the terminal shall be insulated
for a minimum 125V and the insulation shall extend
to within 1mm of the metal terminal throat.
All terminal screws, used or unused, shall be tightened
down.













The Fire Detectors come in 5 temperature set points.
140ºF, 325ºF, 425ºF, 600ºF and 725ºF
The Detectors are color coded for Temperature by bands on the tip of the detector shell 17343-124
No Band is 140ºF
Red Band is 325ºF
Green Band is 425ºF
Orange Band is 600ºF
Gray Band is 725ºF




























INSTALLATION

Refer to the following steps for proper installation of the Heat
Detector assembly:
Recommendation: For best support, use rigid conduit when
installing the heat detector field wiring.
1. After proper mounting of the Heat Detector Housing,
unscrew the enclosure cover, exposing the field wire terminals.
2. Ensure the connections between the Heat Detector and
Terminal Block have not become loose during shipping,
tighten as required.
3. Strip 0.3" (7.6mm) of the insulation from the ends of
Input connection A & B.
4. Insert field wire through port.
5. With a flat tip .14 (3.6mm) screw driver, loosen Input connection
A & B set screw.
6. Insert the exposed end of input connection A and B into
the terminal block as shown.
7. Tighten locking screws hand tight plus 1/4 turn.
8. Thread Heat Detector cover hand tight and tighten.
9. Secure cover in place by tightening the locking set screw
located within the cover with a 1/16 (4.2mm) hex “Allen”
wrench.
















For a Quote, use our Fenwal Parts Form HERE!

Anderson-Bolds
216-360-9800

Fenwal Fire Detectors 17343...Fenwal Fire Detectors 17343...Fenwal Fire Detectors 17343...

Friday, March 2, 2012

Fenwal Detect-A-Fire switches

Anderson-Bolds stocks and sells Fenwal's fire protection Detect-A-Fires.


DETECT-A-FIRE units by Kidde-Fenwal are the "heart" of many Fire Protection Systems. These highly reliable devices have been a standard of the industry for over 45 years. Many thousands of these units are now in use controlling the release of extinguishants such as clean agents, C02, water, or dry chemicals. In some systems the device is used as an ALARM device, to sense overheat or fire, and alert personnel. In other systems, it is used as a RELEASE device, to sense fire and actuate fire attack systems.

DETECT-A-FIRE units by Fenwal Controls have met with wide acceptance because they are designed with RATE COMPENSATION. This provides a unique advantage over both fixed temperature and rate-of-rise types of detectors because only the DETECT-A-FIRE unit accurately senses the surrounding air temperature regardless of the fire growth rate. At precisely the predetermined danger point, the system is activated. Fixed temperature detectors must be completely heated to alarm temperature and therefore a disastrous lag in time may occur with a fast rate fire. Rate-of-rise devices, on the other hand, are triggered by the rate of increase in ambient temperature and are subject to false alarms caused by harmless, transient thermal gradients such as the rush of warm air from process ovens.


The secret of the unit's sensitivity is in the design (Figure 1). The outer shell is made of a rapidly expanding alloy which closely follows changes in surrounding air temperature. The inner struts are made of a lower expanding alloy. Designed to resist thermal energy absorption and sealed inside the shell, the struts follow temperature changes more slowly. A slow rate fire (Figure 2) will heat the shell and struts together. At the "set point," the unit will trigger, actuating the alarm or releasing the extinguishant. A transient rush of warm air up to 40F/min. may expand the shell, but not enough to trigger the unit. By ignoring transient warm air excursions, the DETECT-A-FIRE unit virtually eliminates false alarms prevalent with rate-of-rise devices. If a fast rate fire (Figure 3) starts, the shell will expand rapidly. The struts will close, actuating the alarm or releasing the agent. The faster the fire rate of growth, the sooner the DETECT-A-FIRE unit will react.



HORIZONTAL DETECT-A-FIRE-UNITS
Horizontal detectors are designed for locations where appearance is a factor. The attractive, functional design lends physical protection of the unit while making it suitable for commercial, industrial, mercantile and public buildings,institutions and ships in non-hazardous locations (those classified as "ordinary" under the National Electric Code). Flush mounted units are designed to fit standard 4" octagonal electrical boxes and surface mounting units are designed to mount directly on ceilings or on 4" electrical junction boxes. Canadian Electrical Codes requires mounting only to an electrical junction box.

Fenwal part numbers include: 27020 27021
Temperature Settings (degrees F): 140 160 190 210 225 275 325
VERTICAL DETECT-A-FIRE-UNITS
Vertical detectors are designed for use in both "ordinary" or "hazardous" locations. For "ordinary" use, they may be mounted to any approved junction box with 7/8" diameter opening by using 1/2-14 NPT mounting nuts. The device may be wired in or out of conduit, depending on local preference and codes. Four lead wires are provided on normally open vertical units (that close on temperature rise), per UL requirement, to facilitate supervision of system wiring. Instruments are Underwriters Laboratory and Underwriters Laboratory of Canada listed and Factory Mutual approved for hazardous locations, when mounted in a suitable fitting.

Fenwal Part Numbers include : 27120 28020 27121 28021
Temperature Settings (degrees F): 140 160 190 210 225 275 325 360 450 500 600 750