Showing posts with label Process Oven. Show all posts
Showing posts with label Process Oven. Show all posts

Wednesday, February 10, 2016

Process Ovens Over 40 years Old


Safety Updates for Older Ovens.

 

Most Process ovens made over 40 years ago did not include an excess temperature controller or separate heating element contactors to protect the oven from overheating if the main temperature controller or contactors fail. 
 Any ovens like this should not be used until this safety equipment is installed.  Failure to install this safety equipment could result in the oven overheating and a fire that could result in oven damage, loss of the product load, building damage and injury to personnel.
 

A field kit to add the excess temperature controller and separate contractors should be ordered from the MFG.

The excess temperature controller and separate contactors are now standard equipment on all Grieve ovens.  Also standard is a recirculating blower airflow safety switch to shut down the oven heat if the recirculating blower fails.  This is a pressure differential switch that senses the pressure created when the blower wheel is turning.  This switch protects the oven heating elements by preventing them from heating when air is not being recirculated over them.  A field kit for installation of the recirculating blower airflow safety switch should be purchased from the oven MFG.


When installing new safety equipment it can be a good idea to add other new electronics to the oven for better performance.  New electronics could be a digital temperature controller, programmable digital temperature controller, new thermocouples or a digital timer.  Grieve can provide a field kit to add a digital temperature controllers as well as and a field kit for a digital shut down timer. For electric Ovens new elements can be ordered as well along with pin and sleeve disconnect switches for added electrical safety for personnel. We can provide Gas meters for gas ovens to measure gas flow at the oven and shut the oven down in a dangerous situation.

Grieve's field kits include installation instructions, wiring diagram showing items to be removed, wiring diagram showing items to be added and revised wiring diagram for your records.  Our kits will be based on how the ovens were constructed when they left our factory.  If there have been changes made to the oven in the field they will not be included in our revised wiring diagram.   


Grieve will provide all parts except for standard wire, conduit and conduit fittings.  These items are better provided in the field as necessary to connect the components being added.  Conduit would only be required for the air flow safety switch as the other items are mounted in the oven control panel.

Please contact Anderson-Bolds with the oven serial number, job # and model number all of which can be found on the name plate of the oven.  We can also provide new wiring schematics for old ovens and instruction manuals.  Grieve and Anderson-Bolds want our products to be operated in the safest manner possible. 


Contact Anderson-Bolds at:
216-360-9800 
grieve@anderson-bolds.com


Thursday, October 22, 2015

Grieve Universal 850 Degree Oven

Grieve 2-Compartment Universal Oven

Oven No. 979 is a 85O F (454 C), electrically heated, universal-style
oven from Grieve, currently used for various machine shop heat
treating operations. Workspace dimensions of this oven measure
36" W x 36" D x 36" H in each of the two comparrments. 24 kW
(12 kW per zone) are installed in lncoloy-sheathed tubular elements
to heat the dual oven chambers, while a 6OO-cfm, 1/2-hp
recirculating blower provides front-to-back universal airflow to the
workload in each compartment.
This Grieve universal oven features 6" insulated walls, aluminized
steel exterior with enamel finish, Type 304 stainless steel
interior, double doors, three roller shelves rated for 200-lb loading,
five nickel plated, 100-lb capacity shelves in the top chamber
three nickel plated, 100-lb capacity shelves in the bottom
chamber and an integral leg stand.
No. 979 controls include a digital indicating temperature controller
for each compartment, recirculating blower airflow safety
switches, a 10" diameter circular chart recorder for each compartment
to record part temperature and manual reset excess

temperature controllers with separate contractors.



For more information visit Grieve at Anderson-Bolds or call 216-360-9800

Thursday, December 18, 2014

GRIEVE NBS-400 Bench Oven - Class A

Class A Oven by Anderson-Bolds and Grieve Corporation


Model NBS-400 meets the requirements of OSHA and National Fire Protection Association Standard 86 for Class A ovens. Not for use in hazardous locations as defined in the National Electric Code.

These rugged bench ovens are designed for a wide variety of industrial heat processing applications including those where flammable solvents or vapors will be present in the oven.

STANDARD FEATURES

— Recirculating blower
— 304 stainless steel interior
— Incoloy sheathed tubular heating elements
— Silicone rubber door gasket
— Analog, thermocouple actuated, temperature controller
— Adjustable, thermocouple actuated, manual reset excess
     temperature interlock
— On-off switch
— Red pilot light indicates heater operation
— Sturdy steel construction
— Brushed stainless steel exterior
— 6 lb/cf density industrial rockwool insulation
— Built-in baffles prevent radiant heat
— Fully factory tested
— 1 year limited warranty

MODEL NBS-400
Fan forced recirculation of heated air throughout 7 cubic foot work space at temperatures to 400°F. Includes two (2) removable nickel plated wire shelves easily adjustable on 2" centers. Holds a maximum of seven (7) shelves. Includes safety equipment required when flammable solvents or vapors are present in an oven.

Grieve NBS Class A Bench Oven


STANDARD EQUIPMENT 
Standard Electrical Characteristics
— 208 volts, 1-phase, 60 Hz
— 230 volts, 1-phase, 60 Hz
— Other electrical characteristics available

MODEL NBS-400
Completely wired control panel assembled on the oven enclosing the temperature controller, manual reset excess temperature interlock, pilot light to indicate when heaters are energized and on-off switch. Includes additional safety equipment required by OSHA and NFPA 86 for Class A ovens. Will handle a maximum of 3 ounces (0.024 gallons) of flammable solvents or vapors per batch at a maximum temperature of 400°F. 


Manual Reset Excess Temperature Interlock
Turns off heat if oven exceeds 400°F.

Back-Up Heating Element Relay
Turns off oven heat on excess temperature controller actuation in the
event of failure of the primary heating element relay


35 CFM Separately Powered Forced Exhauster
Provides safety ventilation. Exhaust outlet 4" diameter.


Exhauster Air Flow Safety Switch
Turns off oven heat if exhauster fails


Recirculating Blower Air Flow Safety Switch
Turns off oven heat if recirculating blower fails


Purge Timer
Provides time delay to allow exhauster to pull four oven volumes of
air through the oven prior to turning oven heat on


Contact Anderson-Bolds for all your Electric Processing needs.
We can enhance your production.
216-360-9800