Q'Mark In Floor Unit Heater Model THX

 Q'Mark THX in floor convector Heater from Marley

In-Floor Convector - THX Series

For Information Contact Anderson-Bolds HERE!

THE OUT-OF-SIGHT, OUT-OF-MIND, UL LISTED IN-FLOOR PERIMETER TRENCH HEATER
THX zero vertical profile eliminates visual disruptions while preserving the building’s heat envelope and amplifying building aesthetics. Maximize building comfort and reclaim floor space with the most compact, in-floor convector on the market today.

Brought to you by Marley Engineered Products—a trusted leader in comfort solutions—THX is designed with durability in mind to withstand daily cleaning, water and debris. 

IDEAL SPACES | 
      Conference rooms, Hallways, Lobbies & Offices

Convector Heater for In-Floor Installations
Q'Mark / Marley






PRODUCT INNOVATIONS AND KEY FEATURES |

      Maximize Building Comfort
      THX directly addresses the building's need for supplemental heat against the curtain walls and glazing, while fully integrating with the architects' designed interior spaces. Whether you are starting a new building project or adding to an existing spec, count on the THX to deliver desired performance through unique features and flexible installation options. From design to installation and servicing, the THX is built to be quickly, easily installed and maintained in order to provide the superior comfort solutions your client demands.

      Product Innovations

  • Maintain the building’s heat envelope
  • UL listed out-of-the-box with sealed j-boxes
  • Maximum performance but hidden

      Key Features

  • Easy extensibility
  • Easy mounting
  • Easy installation & maintenance
  • Invisible heat source
  • Rated for high traffic areas

TECHNICAL SPECIFICATIONS |
      Grille Colors

      White, Aluminum & Black

      Grille Types

      Flush or Surface

      Cabinet/Enclosure

  • 16-gauge galvanneal steel enclosure
  • 1/2" and 3/4" electrical knockouts on each end, side and bottom

      Size

  • Low profile 6 1/3" wide by 7 7/8" deep
  • Available in lengths 2' to 5'
  • Standard unit connection kit for lengths beyond 5 ft.

      Heating Volume & Outputs

  • Single phase, 208V, 240V and 277V models available
  • 188 or 250 watts per foot

      Heating Elements

  • Nickle-Chromium wire heating element encased in steel sheath with aluminum fins (standard)
  • Stainless steel heating element with aluminum fins (optional)

      Wiring & Electrical

  • UL Listed with sealed junction boxes
  • All controls included in unit so no need for additional control boxes
  • End connection points and wire-way
  • Dual safety limit chain with both manual and automatic reset

      Water & Debris Management

  • Debris catch screen included
  • UL Listed for water management
  • Elements and connection points are raised off the floor

      Optional Built-In Controls

  • On/Off Switch: for easy and safe servicing
  • Power Relay: for BMS connections
  • Transformer Relay: for remote wall thermostat


THXQ 02188 - 2Ft, 188 watts/Ft., 376 watts, 208, 240, 277 voltages, 30 pounds

THXQ 02250 - 2Ft, 250 watts/Ft., 500 watts, 208, 240, 277 voltages, 30 pounds

THXQ 03188 - 3Ft, 188 watts/Ft., 564 watts, 208, 240, 277 voltages, 40 pounds

THXQ 03250 - 3Ft, 250 watts/Ft., 750 watts, 208, 240, 277 voltages, 40 pounds

THXQ 04188 - 4Ft, 188 watts/Ft., 752 watts, 208, 240, 277 voltages, 52 pounds

THXQ 04250 - 4Ft, 250 watts/Ft., 1000 watts, 208, 240, 277 voltages, 52 pounds

THXQ 05188 - 5Ft, 188 watts/Ft., 940 watts, 208, 240, 277 voltages, 60 pounds

THXQ 05250 - 5Ft, 250 watts/Ft., 1250 watts, 208, 240, 277 voltages, 60 pounds


email to:  qmark@anderson-bolds.com


Anderson-Bolds
216-360-9800
www.anderson-bolds.com

Wednesday, April 17, 2013

Q'Mark Open Coil Duct Heaters


Open Coil Electric Duct Heaters by Q'Mark




 Q'Mark Open Coil Electric Duct Heaters are custom engineered to customer specification and built to order. They are available UL listed in Slip-in or flanged configurations with heavy gauge galvanized steel frame and terminal box construction. There are also NEMA 12 and NEMA 4 models available. Units include primary and secondary thermal protection and are designed for use with vertical up or horizontal airflow in either direction. Alternate constructions are available for oven heaters, round duct, bottom insert and rain tight installations. Elements are constructed using only the highest A-grade 80/20 nickel-chromium resistance wire with stainless steel terminals. Other optional construction features include recessed, dust tight or insulated terminal box, insulated flanges and protective screens.
A wide assortment of built-in control options are available. Exact, not typical, wiring diagrams are provided with each heater.


u CUSTOM ENGINEERED
u HEAT OUTPUT UP TO 2000KW
u 80/20 A GRADE RESISTANCE WIRE
u VARIETY OF CONSTRUCTION STYLES AND OPTIONS
u MANY CONTROL OPTIONS
u APPLICATIONS INCLUDE: 
– OFFICE BUILDINGS 
– INSTITUTIONS 
– RETAIL STORES 
– PRIMARY HEAT IN AIR HANDLING UNITS 
– AUXILIARY HEAT FOR HEAT PUMPS 

SLIP-IN HEATER
Standard and by far the most widely used because
of the ease of installation. When built-in controls are specified in a slip-in heater, they are usually mounted in the left-hand overhang. If right-hand overhang is desired, specify S dimension to be 1”, T dimension as required.
INSTALLATION
Step 1. Cut hole in side of duct 1/8” larger than heater body.
Step 2. Insert heater until terminal box covers opening.
Step 3. Secure heater in place with sheet metal screws.

FLANGED HEATER (Optional)
Consists of a slip-in heater mounted in a flanged duct section. The slip-in portion slides out without removing flanges from duct. When built-in controls are specified in a flanged heater, they are mounted in the terminal box of the slip-in portion; the frame containing the elements stays the same. The flanged duct section is increased in depth to accommodate the larger terminal box.
INSTALLATION
Step 1. Provide flanges on ends of duct matching heater flanges
Step 2. Secure heater flanges to duct flanges with sheet metal screws, so that mounting screws do not enter terminal box.

Part Number Breakdown

OPEN COIL DESIGNATION 
OF Flanged (>81°F Inlet Air) 
OG Flanged (80°F Max Inlet Air) 
OS Slip-In (>81°F Inlet Air) 
OT Slip-In (80°F Max Inlet Air) 
OW Outdoor 
ORS Round Duct (>81°F IA) 
ORT Round Duct >80°F max IA) 
OAF Alt. Flange Slip-In (>81°F IA) 
OAG Alt. Flange Slip-In (80°F max IA) 

MEP VOLTAGE DESIGNATION 
(CONTROL VOLTAGE TO THE UNIT) 
1 24V, 1Ø 
2 120V, 1Ø 
3 208V, 1Ø 
4 240V, 1Ø 
5 277V, 1Ø 

MEP VOLTAGE DESIGNATION 
(SUPPLY VOLTAGE TO THE UNIT & CONTROL VOLTAGE) 
01 24V, 1Ø 
02 120V, 1Ø 
03 208V, 1Ø 
04 208V, 3Ø 
05 240V, 1Ø 
06 240V, 3Ø 
07 277V, 1Ø 
08 480V, 3Ø, 3-wire 
09 480V, 3Ø, 4-wire 

MEP STANDARD CONTROL PACKAGES (SEE CONTROLS BROCHURE FOR PACKAGE DETAILS) 
1 Contains a de-energizing magnetic operating contactor, fuses (heaters > 48 amps), & line-voltage to 24V control transformer. 
2 Contains a de-energizing magnetic operating contactor, fuses (heaters > 48 amps), a line-voltage to 24V control transformer with primary fuses, & electronic step control. 
3 Contains a de-energizing magnetic safety contactor, a de-energizing magnetic operating contactor per step, fuses (heaters > 48 amps), SCR control, SCR Vernier System, & line-voltage to 24V control transformer. 
4 Contains a de-energizing magnetic safety contactor, fuses (heaters > 48 amps), SCR control & line-voltage to 24V control transformer. 
0 Not a standard control package - user defined. 

To calculate the amount of heat required in Kilowatts (KW), knowing the volume of airflow in cubic feet per minute (CFM) and the temperature rise is in degrees Fahrenheit (ΔT) that is required for the application, the required kilowatt (KW) rating of the heater can be determined from the formula:  KW = (CFM x ΔT)/3160

Supply Wire & Terminal Sizing
UL requires the line terminals in duct heaters be sized to accept conductors which are rated to carry at least 125% of heater line cur- rent. Heaters are provided with properly sized terminals at no extra charge. Field supply wires must be sized to carry at least 125% of heater line current except when the heater is for space heating, is over 50 KW, and not more than 3 wires in the conduit. Under those conditions the conductors may be sized at 100% of the heater line current. Supply conductors must have insulation rated at 75°C (167°F) or higher.


Open Coil Duct Heaters 
Open Coil Duct Heaters utilize the highest grade resistance wire in the manufacturing process. An iron-free, 80% nickel and 20% chromium wire has a lower operating temperature, a higher corrosion resistance, less resistance change, less sag, and a longer life expectancy than other commonly used resistance wires. 
For most simple space heating applications, open coil models are a good choice. Open coil models tend to be lower KW and smaller in size than a finned tubular unit. Some of the advantages of an open coil model are: 
• Element Temperature – The open coil element releases its heat directly into the airstream. As a result, the open coil runs cooler than the coil in the finned tubular element which is isolated from the air by insulation and a metal sheath. Because the heat is going directly into the airstream, the duct heats up quicker. 
• Low Pressure Drop – Because of the high percentage of open space across the heater, open coil heaters have very low pressure drop as compared to finned tubular heaters. This can result in reduced fan motor horsepower and makes it possible to retrofit open coil heaters into existing systems without changing the fan motor 
• Large Electrical Clearances – Generous electrical clearances between the coil and frame enable open coil heaters to withstand severe applications such as subway car heating, where voltages may exceed 750 volts. 
• Smaller Size – It is normally possible to get a higher KW with open coil construction for a given face area. 

Q'Mark Open Coil Duct Heaters are UL listed in the USA.

Q'Mark Open Coil Duct heaters are Made in the USA.

Call Anderson-Bolds for more information or for the Ohio or Kentucky wholesaler nearest your location.
216-360-9800 or 513-528-5680



Thursday, February 28, 2013

Q'Mark Artisan Wall Heater

Artisan SmartSeries®-Architectural Digital Wall Heater by Q'Mark, Marley and Anderson-Bolds

The new standard in Wall Heaters.  The Q'Mark SSAR wall heaters.
Programable, stylish, and Energy Efficient.





Q'Mark Artisan SmartSeries® - In a class above the competition – No other heater in the market comes close to the unique styling of the Q'Mark Artisan SmartSeries®.


  • The best in contemporary design matched with the latest Smart technologies - Touch-activated controls offer an ideal combination of sleek styling and ease of operation.
  • Heat where you are, not where you aren’t . Instant response when you want it. Save energy by heating only the areas you occupy.
  • Precise heat within 1.5 degree of set temperature (as compared to five degrees with conventional bi-metal thermostats).
  • 5 day / 2 day programmability (5 weekdays and 2 day weekend, 4 program periods per day).
  • SmartSeries provides only the amount of heat needed at any given moment by continually calculating heat output and fan speed of the proportional difference between room temperature and the set temperature.
  • Built-in fan delay operates when unit is turned off after heating to prolong element life. Fan delay also prevents fan from coming on until element has warmed up.
  • Fan only mode (no heat) for supplemental ventilation.
  • BMS feature allows connection to Building Management Systems (Dry contact).
  • Heater can be locked out for security so settings cannot be changed.
  • Easy to use touch screen operation with adjustable soft signal beeps.
  • Hold mode maintains constant set temperature which can be used for freeze protection or vacation setting for when you are not there.
  • Quick set up – ‘right out of the box’ - 3 piece construction – Includes back box, Element/Fan Deck and Grille.



CATALOG NUMBERVOLTSWATTSAMPSBTUHRWEIGHT
SSAR1802120540 - 1800156,14226
SSAR48082081800 - 480023.116,37826
SSAR48042401800 - 480020.016,37826
SSAR48072771800 - 480017.316,37826




MOUNTING LIMITATIONS
do not install heater closer than 12” to the floor, 12” to an adjacent wall, 36” to the ceiling. do not install heater behind towel rack or door, upside down or sideways, in the floor, in the ceiling, or in closets.






www.anderson-bolds.com
qmark@anderson-bolds.com
216-360-9800